Your home’s defensible space requirements
No guessing. No waiting. No commitment.
Preview · LACoFD · Very High (LRA)
123 Example Lane, Example City, CA 00000
APN: 000-000-000
Defensible space required- Fire Authority
LACoFD’s Defensible Space Unit enforces the Fire Code’s brush clearance requirements on improved parcels in unincorporated Los Angeles County and its contract cities, including Agoura Hills, Calabasas, Hidden Hills and Westlake Village. LACoFD program; 2026 Annual Notice
Questions before your inspection: Defensible Space Unit, (626) 969-2375, fire-defensiblespace@fire.lacounty.gov. After your inspection, call the number on your inspection report. 2026 FAQs
Sources: LACoFD · Defensible Space program · LACoFD · 2026 Annual Defensible Space FAQs
- Fire Hazard Severity Zone
A fire hazard severity zone is an area mapped by CAL FIRE as Moderate, High or Very High based on its potential for wildfire over time. The classification considers vegetation, terrain and weather; it is not a score for your home.
Where state defensible space law applies:
• State Responsibility Area (SRA), any zone (Moderate, High or Very High): required by Public Resources Code §4291. PRC §4291(a)
• Local Responsibility Area (LRA), Very High zone: required by Government Code §51182. Gov. Code §51182(a)
• LRA Moderate or High zone: not covered by the state defensible space mandate. Your fire authority’s local code can still require clearance, for example where the property is in its annual inspection program.
Sources: CAL FIRE · Fire Hazard Severity Zones · Public Resources Code §4291 · Government Code §51182
- Annual compliance notice
Los Angeles County Fire mails its annual Defensible Space Inspection Program notice (the Annual Defensible Space Clearance Notice) in the third week of February, after the Board of Supervisors approves the year’s inspection list. 2026 Program Details
The notice goes to parcels on the inspection (Declaration) list: properties in a Fire Hazard Severity Zone or identified by the Fire Department as having a potential fire hazard. The 2026 notice is dated February 1, 2026. 2026 Annual Notice; 2026 FAQs
The notice is not a citation or summons. Owners who believe their parcel should not be inspected may contest it at a referee hearing in late February. 2026 Annual Notice
Sources: LACoFD · 2026 Defensible Space Inspection Program Details · LACoFD · 2026 Annual Defensible Space Clearance Notice · LACoFD · 2026 Annual Defensible Space FAQs
- Annual inspection start date
The annual inspection start date is when the fire authority begins inspecting properties in your area. 2026 Annual Notice
For 2026, inspections began approximately April 1 in desert communities, May 1 in inland communities and June 1 in coastal communities. These are inspection start dates, not a countywide compliance deadline or an appointment for your home. 2026 Annual Notice; 2026 FAQs
Property owners do not need to be home for the inspection. 2026 FAQs
An Official Inspection Report identifies any violations and sets a correction deadline. Noncompliant owners receive at least 30 days to correct violations before follow-up. 2026 Annual Notice; 2026 FAQs
Required defensible space must be maintained year-round. LACo Fire Code §325.2.1; PRC §4291
Sources: LACoFD · 2026 Annual Defensible Space Clearance Notice · LACoFD · 2026 Annual Defensible Space FAQs · Los Angeles County Fire Code §325.2.1
Preview · VCFD · High (SRA)
123 Example Lane, Example City, CA 00000
APN: 000-000-000
Defensible space required- Fire Authority
VCFD’s Fire Hazard Reduction Program (FHRP) covers all of Ventura County except the cities of Ventura, Oxnard and Fillmore. VCFD FHRP
Questions: FHRP, 805-389-9759, fhrp@venturacounty.gov. VCFD FHRP
Sources: VCFD · Fire Hazard Reduction Program
- Fire Hazard Severity Zone
A fire hazard severity zone is an area mapped by CAL FIRE as Moderate, High or Very High based on its potential for wildfire over time. The classification considers vegetation, terrain and weather; it is not a score for your home.
Where state defensible space law applies:
• State Responsibility Area (SRA), any zone (Moderate, High or Very High): required by Public Resources Code §4291. PRC §4291(a)
• Local Responsibility Area (LRA), Very High zone: required by Government Code §51182. Gov. Code §51182(a)
• LRA Moderate or High zone: not covered by the state defensible space mandate. Your fire authority’s local code can still require clearance, for example where the property is in its annual inspection program.
Sources: CAL FIRE · Fire Hazard Severity Zones · Public Resources Code §4291 · Government Code §51182
- Annual compliance notice
VCFD mails annual Notices to Abate Fire Hazard on April 20 to properties in its Fire Hazard Reduction Program. VCFD FHRP; Guideline 411
Parcels are included when, for example, natural vegetation is within 100 feet of a structure, the parcel has a fuel modification zone, or it is in a State Responsibility Area, a Local Responsibility Area Very High zone, or a VCFD Hazardous Fire Area. Guideline 411
VCFD may send an additional notice later in the year if the fire station requires regrowth to be removed. Guideline 411
Sources: VCFD · Fire Hazard Reduction Program · VCFD Guideline 411 · FHRP FAQ (Apr 20, 2026)
- Annual inspection start date
The annual clearance deadline is June 1. Long-term extensions are not granted. Guideline 411
Local fire stations normally start property inspections the last week of May and continue into June; completing all inspections can take several weeks. Guideline 411
Participating properties are expected to remain free of fire hazards or nuisance vegetation year-round. VCFD FHRP
If the required clearance is not done by the deadline, VCFD’s contractor may do the work, and the cost plus an administrative fee is placed on the property as a special assessment lien. Guideline 411
Check whether your parcel’s clearance has been approved, and get a Receipt of Approval, at fhrpreceipt.venturacounty.gov (updated each morning). Guideline 411
Sources: VCFD Guideline 411 · FHRP FAQ (Apr 20, 2026) · VCFD · Fire Hazard Reduction Program · VCFD · Parcel approval lookup
Preview · VCFD · Moderate (LRA) · no inspection
No defensible space inspectionThis property is in a Moderate Fire Hazard Severity Zone in a Local Responsibility Area (LRA).
State defensible space law applies in LRA Very High zones, so this property has no state defensible space requirement or annual inspection based on its zone. VCFD can still include a parcel in its Fire Hazard Reduction Program, for example where natural vegetation is within 100 feet of a structure; if you receive a Notice to Abate Fire Hazard, its requirements apply. Gov. Code §51182; Guideline 411
Read the FAQPreview · VCFD · High (LRA) · no inspection
No defensible space inspectionThis property is in a High Fire Hazard Severity Zone in a Local Responsibility Area (LRA).
State defensible space law applies in LRA Very High zones, so this property has no state defensible space requirement or annual inspection based on its zone. VCFD can still include a parcel in its Fire Hazard Reduction Program, for example where natural vegetation is within 100 feet of a structure; if you receive a Notice to Abate Fire Hazard, its requirements apply. Gov. Code §51182; Guideline 411
Read the FAQPreview · LACoFD · Moderate (LRA) · no inspection
No defensible space inspectionThis property is in a Moderate Fire Hazard Severity Zone in a Local Responsibility Area (LRA).
State defensible space law applies in LRA Very High zones, so this property has no state defensible space requirement or annual inspection based on its zone. LACoFD can still place a parcel on its annual inspection list when the Fire Department identifies a potential fire hazard; if you receive an Annual Defensible Space Clearance Notice, its requirements apply. Gov. Code §51182; LACoFD 2026 FAQs
Read the FAQPreview · LACoFD · High (LRA) · no inspection
No defensible space inspectionThis property is in a High Fire Hazard Severity Zone in a Local Responsibility Area (LRA).
State defensible space law applies in LRA Very High zones, so this property has no state defensible space requirement or annual inspection based on its zone. LACoFD can still place a parcel on its annual inspection list when the Fire Department identifies a potential fire hazard; if you receive an Annual Defensible Space Clearance Notice, its requirements apply. Gov. Code §51182; LACoFD 2026 FAQs
Read the FAQPreview · Not in a mapped zone
Not in a Fire Hazard Severity ZoneThis property is not in a mapped Fire Hazard Severity Zone.
Zone-based state defensible space rules do not apply. Your fire authority can still include the property in its annual inspection program, for example where natural vegetation is within 100 feet of a structure. If you receive an annual notice, its requirements apply.
Read the FAQPreview · Address not found
Address not foundWe couldn’t match that address.
Check the street number, street name and city, then try again. A missing result does not mean the property has no defensible space requirements. You can also locate the property on CAL FIRE’s Fire Hazard Severity Zone map.
Open CAL FIRE’s mapPreview · System error
Lookup unavailableSomething went wrong on our end.
The Snapshot couldn’t complete this lookup. Nothing was saved. Please try again in a few minutes, or call (805) 818-8218 if your inspection or deadline is close.
Call 805-818-8218Preview · Outside service area
Outside our service areaThis address is outside the area the Snapshot covers.
The Defensible Space Snapshot covers properties served by the Ventura County Fire Department and the Los Angeles County Fire Department. This address is served by another fire authority.
See our service areaPreview · Needs confirmation
Needs confirmationWe couldn’t confirm this property’s zone automatically.
CAL FIRE has changed its Fire Hazard Severity Zone data since we last verified it, so we won’t guess. Check CAL FIRE’s map, or book a consultation and we’ll check with your fire authority and share what we find.
Open CAL FIRE’s mapMaintenance requirements
Plain-English summary of what VCFD’s adopted Wildland-Urban Interface Code and Defensible Space Standard require around a home, organized by zone. Each requirement cites its section, and the cited code section controls.
Requirements last verified October 23, 2026 · Situation: existing home
Zone 0 · 0–5 feet · existing homes
- Zone 0 is the first 5 feet around the building, decks, patio covers, balconies and stairs, and includes the roof and the areas on top of and underneath decks. VCWUIC §604.8.2
- Roofs and gutters must be kept free of leaves, needles and other vegetative combustible material. §604.8.2.3.1(5)
- Trees and vegetation must have at least 3 feet of vertical clearance above any roof. §604.8.2.3.1(6)
- Trees and vegetation must stay at least 3 feet to the side of, above and below any eave or roof projection, including patio covers and other building projections. §604.8.2.3.1(7)
- No combustible landscape mulch or wood chips, no firewood, and no artificial or synthetic grass. §604.8.2.3.1(1, 2, 8)
- No vegetation underneath decks; remove other combustible materials stored under decks. §604.8.2.3.1(3, 4)
- No new trees. New or replacement landscaping must meet the new-building Zone 0 rules. §604.8.2.3.1(9, 10)
- Landscaped roofs are prohibited. §604.8.2.3.2
- Fencing within 5 feet: fences installed before January 1, 2023 may remain, but if any part is replaced, the entire fence within 5 feet (including gates) must be non-combustible. §604.11.3
Zone 0 · new buildings, additions & new landscaping
- Since March 1, 2025, all fuels, including combustible materials and vegetation, are prohibited in Zone 0 for new buildings, additions, new landscaping and refurbished landscaping. §604.8.2.1
- No tree canopies within 10 feet of a new building or addition. Existing protected oaks must be trimmed to at least 5 feet above and 5 feet to the side of it. §604.8.2.2(1)
- No vegetation on or under decks or on balconies; no planting boxes within 5 feet; no vines or climbing plants on structures or on fences within 5 feet. §604.8.2.2(3–8)
- All fencing and gates within 5 feet must be non-combustible (required for any fence installed on or after January 1, 2023). §604.8.2.2(11), §604.11.2
Zone 1 · 5–30 feet
- Extends 5–30 feet from structures and decks, or 5–50 feet where slopes exceed 20%. Includes a transitional area within 5 feet of Zone 0 (10 feet on slopes over 20%). §604.8.3, §604.8.3.1
- Plants and vegetation must follow VCFD’s Defensible Space and Fuel Modification Standards. For new or replacement landscaping, single shrubs in the transitional area may not exceed 2 feet in height. §604.8.3.2; Std. 515
- New trees: crowns must be at least 20 feet from the crowns of adjacent trees at maturity. §604.8.6.5.1
- Firewood in Zone 1 must be completely enclosed in a secured, fire-resistant enclosure at least 5 feet from any building. Each pile is limited to 125 cubic feet and 4 feet high, and total firewood in Zones 1 and 2 to 250 cubic feet. §607.1.1
Zone 2 · to 100 feet
- Extends from the outer edge of Zone 1 to 100 feet from structures and decks. §604.8.4
- New trees: crowns must be at least 10 feet from the crowns of adjacent trees at maturity. §604.8.6.5.1
- Spacing at the outer edge of Zone 2 is based on the height of vegetation in Zone 2 or beyond the 100-foot line, whichever requires more. This can require clearance beyond 100 feet. §604.8.4.2
- Exposed firewood piles must have 10 feet of clearance to bare mineral soil in all directions. §607.1.1
- Other stored combustible materials: piles no larger than 100 square feet and 10 feet high, separated by at least 20 feet. §607.1.2
Zone 3 · beyond 100 feet
- A thinning zone beyond 100 feet, required where set by conditions of development or by the Fire Department. §604.8.5
All zones (0–100 feet)
- Remove all dead or dying grass, plants, shrubs, trees, branches, leaves, weeds and tree needles. §604.8.6.1
- Natural or annual grasses must be mowed to a maximum 3-inch stubble, with clippings removed. §604.8.6.7
- Combustible mulch and wood chips in Zones 1 and 2 may not exceed 3 inches in depth and must be kept 12 inches from tree trunks and combustible fences. §604.8.6.2; Std. 515 §4.4
- Combustible materials may not be stored in unenclosed spaces beneath buildings, on decks, or under eaves, canopies or other overhangs. §607.1
- The owner of the land within the 100-foot zone is responsible for its clearance, including abutting County road right-of-way. §604.3.2, §604.3.2.1
Trees
- Remove any part of a tree or shrub within 10 feet horizontally or vertically of a chimney or stovepipe outlet. §604.8.6.4
- Trees taller than 6 feet must be limbed up 6 feet or one-third of their height, whichever is less (fruit trees when approved). §604.8.6.5.2
- Under tree canopies: the lowest branch must be at least three times the height of the ground cover or shrub beneath it, and ground cover must be kept 3 feet from the trunk. §604.8.6.5.3
- New trees: the drip line at maturity must be at least 10 feet from any combustible structure. §604.8.6.5
- Existing homes built before April 1, 2019: continuous tree canopies are allowed only if the Fire Code Official approves, with all understory removed and remaining trees limbed up 12 feet or one-third of their height. §604.8.6.6.2
Access, utilities & equipment
- Maintain at least 13 feet 6 inches of vertical clearance above roads, driveways, turnouts and turnarounds that provide fire department access. Std. 515 §4.5.3
- Where required by the Fire Code Official, clear non-fire-resistive vegetation for 10 feet on each side of fire apparatus access roads and driveways. Std. 515 §4.5.4
- Keep at least 3 feet of horizontal and 8 feet of vertical clearance around fire hydrants and fire department water outlets. Std. 515 §4.5.5
- Propane (LP-gas) tanks: 10 feet of clearance to bare mineral soil in all directions; vegetation 10–20 feet away must be fire-smart. §606.3
- Chimneys serving fireplaces, barbecues or other solid- or liquid-fuel appliances need a spark arrestor with openings no larger than ½ inch. §605.1
- No vegetation may be planted under or near power lines that will grow within 10 feet of the energized conductors. §604.10
- Annual program: Notices to Abate Fire Hazard are mailed April 20; the clearance deadline is June 1; property must be kept clear year-round. VCFD FHRP
Need to pass a VCFD defensible space inspection?
You don’t have to become a wildfire expert or construction project manager to make your home wildfire compliant. Bring us the problem. We assess your home, tailor a scope of work, complete that work promptly and deliver the final documentation. One contract, one point of contact. Done.
Book a ConsultationMaintenance requirements
Plain-English summary of what the Los Angeles County Fire Code and state law require around a home in LACoFD’s jurisdiction, organized by zone. Each requirement cites its section, and the cited code section controls.
Requirements last verified October 23, 2026 · Situation: existing home
Zone 0 · 0–5 feet, roof & chimney
- There is no Zone 0 (ember-resistant zone) rule in effect. State law calls for one; no state rule is in effect as of October 23, 2026. PRC §4291(a)(1); OAL 2026-0828-03E
- Keep the roof and rain gutters free of leaves, needles and other dead vegetative growth. LACo Fire Code §325.2.1.4; PRC §4291(a)(4)
- Remove any part of a tree that extends within 10 feet of the outlet of a chimney or stovepipe. §325.2.1.5; PRC §4291(a)(2)
- Keep any tree or shrub adjacent to or overhanging the building free of dead wood. §325.2.1.3; PRC §4291(a)(3)
Zone 1 · 0–30 feet
- Store firewood, manure, compost and similar combustible materials at least 30 feet from any building or structure. §325.2.1.6
- Ornamental plants and trees known to be flammable, including acacia, cedar, cypress, eucalyptus, juniper, pine and pampas grass, are not exempt. They may remain only if individually planted, spaced and maintained so they cannot carry fire from native growth to the structure. §325.2.1.1
- LACoFD’s annual notice applies this as: remove those species within 30 feet of any structure (50 feet in extra hazard areas), or keep them free of dead material and trimmed away from the structure. 2026 Annual Notice
Zone 2 · 30–100 feet
- Maintain defensible space for 100 feet from each side and the front and rear of every structure, with fuels spaced so a wildfire under average weather conditions would be unlikely to ignite the structure. §325.2.1; PRC §4291(a)(1)
- The annual notice applies this as: thin remaining vegetation for the next 70 feet, for a total of 100 feet, by clearing, trimming, thinning, limbing up and removing combustible vegetation and dead wood. 2026 Annual Notice
- Exposed woodpiles within 100 feet of a building need 10 feet of clearance to bare mineral soil in all directions. §325.2.1.6
- Beyond 30 or 50 feet (as the fire code official determines), loose surface litter such as leaves, needles, twigs and small branches may remain up to 6 inches deep. §325.2.1.3 exception
Zone 3 · extra hazard areas
- Where the fire code official finds 100 feet insufficient, owners can be notified to clear for a greater distance, up to 200 feet. §325.2.1 exception 1
All zones (0–100 feet)
- Remove all dead or dying grass, plants, shrubs, trees, branches, leaves, weeds and pine needles. This includes cured annual grass; the code sets no grass height. §325.2.1.3
- Cultivated ground cover such as green grass, ivy and succulents may remain if maintained so it cannot carry fire from native growth to the structure. §325.2.1.2
- Clearance is required only where the owner has the legal right to clear; no one is required to enter or alter a neighbor’s property without consent. §325.2.1 exception 2
Access & roads
- Fire apparatus access roads must have unobstructed vertical clearance clear to the sky. For protected tree species next to the road, a minimum of 13 feet 6 inches may be allowed, with any required tree-trimming permit. §503.2.1
- The fire code official may require all flammable vegetation to be cleared for at least 10 feet on each side of every public or private roadway; the annual notice applies 10 feet of brush clearance on each side of fire access roads. §325.10; 2026 Annual Notice
- Provide at least 3 feet of brush clearance around all fire hydrants. 2026 Annual Notice
- Enforcement (2026): inland inspections begin May 1. Owners have 30 days to correct violations; failing to comply brings a $500 fine plus a $1,647 enforcement assessment. The $151 inspection fee is billed on the following year’s property tax bill. Check current amounts with LACoFD. 2026 Annual Notice
Official sources
- Los Angeles County Code Title 32 (Fire Code) §325 · Clearance of brush and vegetative growth
- Los Angeles County Fire Code §503.2.1 · Access road dimensions
- LACoFD · Annual Defensible Space Clearance Notice 2026
- LACoFD · 2026 Annual Defensible Space FAQs
- Public Resources Code §4291
- Government Code §51182
- Office of Administrative Law · Zone 0 emergency rule (2026-0828-03E), withdrawn
Need to pass a LACoFD defensible space inspection?
You don’t have to become a wildfire expert or construction project manager to make your home wildfire compliant. Bring us the problem. We assess your home, tailor a scope of work, complete that work promptly and deliver the final documentation. One contract, one point of contact. Done.
Book a ConsultationWhat this Snapshot is, and isn’t
Informational only. The Defensible Space Snapshot is a free lookup of public records. It is not legal advice, an inspection, a compliance determination, a certification or proof of compliance. It does not replace any inspection, notice or documentation from your fire authority.
No relationship. Using this tool or receiving its report does not make you our client or create a consulting, advisory or contractor relationship. That relationship begins only with a paid consultation or a signed contract.
Source and date. Fire hazard zones come from CAL FIRE’s Fire Hazard Severity Zone maps (LRA map dated March 24, 2025; SRA map effective April 1, 2024). Fire authority and parcel information come from public agency records. All were checked on the date shown on your report. Maps, parcel matches and agency information can be incomplete or out of date, and agencies can change or interpret their rules. Where we can’t verify something, we say so.
What a result doesn’t tell you. A hazard zone describes an area’s wildfire potential, not your home’s condition. A result does not establish a passing inspection, an inspection date, insurance acceptance, a premium discount. A result showing no requirement does not mean the property has none. Your fire authority can still require clearance, and its notices control.
Your decisions. Confirm requirements, deadlines and accepted documentation with your fire authority before you act. You are responsible for the decisions you make using this tool. To the extent the law allows, Mustard Construction is not liable for those decisions or for decisions by fire authorities, insurers, lenders or others. Nothing here limits liability the law does not allow us to limit. Our Terms of Use apply.
Sample report. The sample report shown on this page describes a fictional property and is for illustration only.